ICP DAS USA MSM-508FC Switch User Manual


 
Industrial Redundant Ring Switch – Managed Switch Console Manual
Release No. : 0804-V1 12
Example
RTIME [time]
Description
Recovery time is the length of time it takes to return back to normal operation after an error
or other failure has occurred. This command enables you to set up the recovery time in
millisecond (ms).
Parameters
Parameter Description
time Provides the time interval(ms) that you want to set up as the
recovery time
Example
Return message: “recovery time X (Y) ms. ”
“X” ( switch value) indicates the rtime value set by console command,
“Y” (operating value) indicates the actual operating value.
Value can be specified only on Cyber-Ring Protocol Mode (refer to HMIVLAUE setting).
NOTE
Use the following function to calculate an adequate rtime:
rtime = [Round(0.3*(N+1))]*100 ms
N: number of switches
Example:
If there are 5 switches (including master switch), the adequate rtime will be: