Kohler 60RCL Tablet Accessory User Manual


 
TP-6810 11/1316 Section 2 Generator Set Operation
2.3 Exercising the Generator Set
Operate the generator set without load every week or
every other week for 20 minutes. Perform all o f the
prestart checks before starting the exercise procedure.
See Section 2.5 for instructions to set the automatic
exerciser.
2.4 Generator S et Operation
2.4.1 Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.2 Automatic Starting and Stopping
An automatic transfer switch monitors the utility power
and signals the generator set to start when utility power
is lost. The ATS then transfers the load to the generator
set.
When utility power is restored, the transfer switch
transfers the load back to utility, runs the generator set
with no load to cool down the engine, and then stops the
generator set engine. The electric fans continue to run
for two minutes after the engine shuts down to evacuate
the engine compartment.
2.4.3 Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.4.4 Engine Start Crank Cycle
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an overcrank
fault. See Section 2.6.
Pressing the OFF button during the crank cycle stops
the cranking. No other buttons are acknowledged
during the crank cycle.
2.4.5 Engine Cooldown
The engine cooldown time delay allows the engine to
run after the loads have been removed.
The engine cooldowntime delay is set to 5 minutes.The
engine stops before the cooldown time delay expires if
the temperature drops below the cooled-down
temperature level, or if the temperature rises above the
high limit during the cooldown cycle.
Theelectric fanscontinueto runfortwominutes afterthe
engine shuts down to evacuate the engine
compartment.
If a transfer switch other than the Model RXT is used, an
additional engine cooldown time delay may be
programmed on the transfer switch. To allow the smart
engine cooldown on the RDC2 controller to operate
most efficiently, set the cooldown time on the transfer
switch controller to zero or the minimum time allowed.
Refer to the instructions provided with the transfer
switch for more information.
2.4.6 Automatic Operation with Mod el
RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2
controller through the ATS interface board on the
transfer switch. Also see Section 2.7, Model RXT
Transfer Switch Operation.
The RDC2 controller must be in AUTO mode for
automatic transfer switch operation.
Automatic Start
The RDC2 controller receives utility source voltage
sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an
acceptable level, the controller starts the engine
start time delay.
2. If the utility source is not restored before the time
delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the
ATS is signaled to transfer the load to the
emergency source.