Liebert 115V Power Supply User Manual


 
8
115V SPECIFICATIONS
Model Number PSA350-120 PSA470-120 PSA700-120
Model Rating VA/W 350VA/210W 470VA/282W 700VA/420W
DIMENSIONS: in (mm)
Unit
H x W x D
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
Shipping
H x W x D
8.8 x 6.2 x 15.8
(226 x 156 x 404)
8.8 x 6.2 x 15.8
(226 x 156 x 404)
8.8 x 6.2 x 15.8
(226 x 156 x 404)
WEIGHT: lbs (kg)
Unit 13.2 (6) 15.4 (7) 22 (10)
Shipping 15 (6.8) 17.2 (7.8) 23.8 (10.8)
INPUT AC PARAMETERS
Voltage Range
without Battery Operation
87 to 144VAC
Line to Boost Transfer 104VAC
Line to Buck Transfer 124VAC
Frequency 47-53 Hz or 57-63 Hz; auto sensing
Input Power Cord 6 ft. detachable, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles (4) 5-15R
Voltage (Battery Mode) 115 VAC + 5%
Waveform (Battery Mode) Stepped Sinewave
Voltage (Normal) V
IN
* (1.0)
Voltage (Boost Mode) V
IN
* (1.16)
Voltage (Buck Mode) V
IN
* (0.84)
Frequency 50 Hz or 60 Hz; auto sensing
Overload Warning
(Utility and Battery Modes)
101 – 120%
Overload Shutdown
(Utility and Battery Modes)
Overload
+ (15 – 30W)
Overload
+ (20 – 40W)
Overload
+ (30 – 60W)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating (1) x 12V x 7.0 Ah (1) x 12V x 7.0 Ah (1) x 12V x 10 Ah
Approved Battery
Manufacturers:
CSB, Panasonic, and Yuasa
Transfer Time 4 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 5 minutes typical
Back-up Time:
Full load
Half load
> 15 minutes typical > 12 minutes typical > 13 minutes typical
Recharge Time 7-10 hours to 90% capacity, after full discharge into 100% resistive load
ENVIRONMENTAL
Operating Temperature +32° F to + 104° F (0° C to +40° C)
Storage Temperature +5° F to + 122° F (-15° C to +50° C)
Relative Humidity 0% to 90%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating
Audible Noise < 40 dBA, at 1 meter
AGENCY
Safety UL 1778, c-UL Listed
Surge IEEE C62.41 Category A
ESD IEC 801-2, Level 3, Criterion< 2
Susceptibility IEC 801-3, Level 3, Criterion< 2
Electrical Fast Transient/Burst IEC 801-4, Level 4, Criterion< 2
Emissions FCC Part 15, Subpart B, Class B
Transportation ISTA Project 1A