Liebert 115V Power Supply User Manual


 
9
230V SPECIFICATIONS
Model Number PSA350-230 PSA470-230 PSA700-230
Model Rating VA/W 350VA/210W 470VA/282W 700VA/420W
DIMENSIONS: mm (in)
Unit
H x W x D
166 x 115.5 x 352.5
(6.5 x 4.5 x 13.9)
166 x 115.5 x 352.5
(6.5 x 4.5 x 13.9)
166 x 115.5 x 352.5
(6.54 x 4.55 x 13.9)
Shipping
H x W x D
226 x 156 x 404
(8.8 x 6.2 x 15.8)
226 x 156 x 404
(8.8 x 6.2 x 15.8)
226 x 156 x 404
(8.8 x 6.2 x 15.8)
WEIGHT: kg (lbs)
Unit 6 (13.2) 7 (15.4) 10 (22)
Shipping 6.8 (15) 7.8 (17.2) 10.8 (23.8)
INPUT AC PARAMETERS
Voltage Range without
Battery Operation
166 to 275VAC
Line to Boost Transfer 198VAC
Line to Buck Transfer 250VAC
Frequency 47-53 Hz or 57-63 Hz; auto sensing
Input Power Receptacle EN60320/C14 recessed plug
OUTPUT AC PARAMETERS
Output Receptacles (4) EN60320/C13 sockets, (2) detachable EN60320-2-2 1.8m (6’) power
cords
Voltage (Battery Mode) 230 VAC + 5%
Waveform (Battery Mode) Stepped Sinewave
Voltage (Normal) V
IN
* (1.0)
Voltage (Boost Mode) V
IN
* (1.13)
Voltage (Buck Mode) V
IN
* (0.85)
Frequency 50 Hz or 60 Hz; auto sensing
Overload Warning
(Utility and Battery Modes)
101 – 120%
Overload Shutdown
(Utility and Battery Modes)
Overload
+ (15 – 30W)
Overload
+ (20 – 40W)
Overload
+ (30 – 60W)
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating (1) x 12V x 7.0 Ah (1) x 12V x 7.0 Ah (1) x 12V x 10 Ah
Approved Battery
Manufacturers:
CSB, Panasonic, and Yuasa
Transfer Time 4 – 6 ms typical
At 25°C (77°F), resistive loading, with fully charged batteries:
> 5 minutes typical
Back-up Time:
Full load
Half load
> 15 minutes typical > 12 minutes typical > 13 minutes typical
Recharge Time 7-10 hours to 90% capacity, after full discharge into 100% resistive load
ENVIRONMENTAL
Operating Temperature 0° C to +40° C (+32° F to + 104° F)
Storage Temperature -15° C to +50° C (+5° F to + 122° F)
Relative Humidity 0% to 90%, non-condensing
Operating Elevation Up to 3000 m. (10,000 ft) at 35° C (95° F) without derating
Audible Noise <40 dBA, at 1 meter
AGENCY
Safety EN50091-1, TUV/GS listed, CE Compliance Mark
Surge IEC 801-5, Level 3
ESD IEC 801-2, Level 3, Criterion< 2
Susceptibility IEC 801-3, Level 3, Criterion< 2
Electrical Fast
Transient/Burst
IEC 801-4, Level 4, Criterion< 2
Emissions EN50091-2, EN55011 Class B
Transportation ISTA Project 1A