Liebert FS-8704-02 Network Card User Manual


 
FS-8704-02_BacnetEthernet.doc Driver Manual Page 14 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
5.4.3. Map Descriptor Example
// Server Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Object_Type, Object_Instance Property, Units, Relinquish_Default
SMD_AI_01, DA_AI_01, 0, Server, Virtual_BCU_11, AI, 1, Present_Value, Degrees-Fahrenheit, -
SMD_AI_02, DA_AI_01, 1, Server, Virtual_BCU_11, AI, 2, Present_Value, Degrees-Fahrenheit, -
SMD_AI_03, DA_AI_01, 2, Server, Virtual_BCU_11, AI, 3, Present_Value, Degrees-Fahrenheit, -
SMD_AO_01, DA_AO_01, 0, Server, Virtual_BCU_11, AO, 1, Present_Value, percent-relative-humidity, 0
SMD_AO_02, DA_AO_01, 1, Server, Virtual_BCU_11, AO, 2, Present_Value, percent-relative-humidity, 0
SMD_AO_03, DA_AO_01, 2, Server, Virtual_BCU_11, AO, 3 Present_Value, percent-relative-humidity, 0
// Server Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Object_Type, Object_Instance, Property Relinquish_Default
SMD_DI_01, DA_DI_01, 0, Server, Virtual_BCU_11, DI, 1, Present_Value -
SMD_DI_02, DA_DI_01, 1, Server, Virtual_BCU_11, DI, 2, Present_Value -
SMD_DI_03, DA_DI_01, 2, Server, Virtual_BCU_11, DI, 3, Present_Value -
SMD_DO_01, DA_DO_01, 0, Server, Virtual_BCU_11, DO, 1, Present_Value 0
SMD_DO_02, DA_DO_01, 1, Server, Virtual_BCU_11, DO, 2, Present_Value 0
SMD_DO_03, DA_DO_01, 2, Server, Virtual_BCU_11, DO, 3, Present_Value 0