Liebert GXT 2U Power Supply User Manual


 
Installation
8
4.0 INSTALLATION
4.1 PREPARATION
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
2. Decide where to place the GXT 2U. Install the UPS indoors in a
controlled environment, where it cannot be accidentally turned off.
Place it in an area of unrestricted airflow around the unit, away
from water, flammable liquids, gases, corrosives, and conductive
contaminants. Maintain a minimum clearance of 4 in. (100mm) in
the front and rear of the UPS. Maintain an ambient temperature
range of 32°F to 104°F (0°C to 40°C).
3. The GXT 2U may be installed in either a tower configuration or in
a rack, depending on available space and use considerations.
Determine the type of installation and follow the appropriate
instructions in either 4.2 - Tower UPS Installation or 4.3 -
Rack-Mount UPS Conversion and Installation.
4.2 TOWER UPS INSTALLATION
When using the GXT 2U in a tower configuration, use the included
support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accom-
modate the additional cabinets (shown below, right).
!
CAUTION
The UPS is heavy (see 11.0 - Specifications). Take proper
precautions when lifting or moving it.
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
Support base Spacers added to support
base to accommodate
additional battery cabinets