Liebert Integrated Secured Protection Surge Protector User Manual


 
11
TABLES
FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)
AIRFLOW (w/Filter) SOUND LEVEL INPUT POWER (1PH)
FLA / WSA / OPD
MODEL #
# FANS
HIGH
SPEED
LOW
SPEED
HIGH
SPEED
LOW
SPEED
120V/60Hz 220V/50Hz
FAC-190 1
190 CMF
112 CMH
90 CMF
53 CMH
61 dBa 47 dBa 0.5/15/15 0.5/15/15
FAC-360 2
360 CMF
212 CMH
175 CMF
103 CMH
59 dBa 49 dBa 1.0/15/15 1.0/15/15
ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA
RATED
CAPACITY
SUPPORT
LOAD
RATED/MAX
AMBIENT
HEIGHT
DIMENSIONS
WIDTH
DEPTH
TOTAL
HEAT REJ.
INPUT POWER (1PH) WEIGHTMODEL
NUMBER
BTUH/Watt BTUH/Watt 60Hz 50Hz U
In/mm In/mm Rack In/mm
BTUH/Watt
120V/60Hz 220V/50Hz
(lbs/Kg)
ECM-42 4200/1230 2730/800 105F
41C
100F
38C
6 10.5/
265
17.5/
445
19 27/
685
7625/
2235
8/15/15 7/15/15 95/43
ECM-62 6200/1815 4095/1200 105F
41C
100F
38C
7 12.3/
310
22/
560
24 27/
685
11310/
3315
12/20/20 9/15/15 115/52
ECM-80 8000/2345 5800/1700 105F
41C
100F
38C
9 15.8/
400
22/
560
24 29/
735
14605/
4280
16/20/20
16/20/20
167/76
ECM Notes: Standard Offerings - All Systems
1. 60Hz: R-22 refrigerant / 50Hz: R-134A refrigerant
2. Two-Speed Operation - Switch low-high speed on ambient temperature external to LGH enclosure
3. Automatic Load Matching: Hot gas by-pass factor set for minimum capacity; by-pass will adjust to
match supported loads
4. Condensate Re-evaporation & Removal: Drain connection only required if enclosure seal is violated.