Liebert Integrated Secured Protection Surge Protector User Manual


 
12
Electrical Service / Connection
The 60 Hz LGH is provided with a single NEMA plug and cord input power connection (except for ECM-
80 systems).
60 Hz Systems with UPS - Service Connection
If a UPS is supplied, the system power rating and plug connection are fixed.
FIXED SERVICE CONNECTION (AMPS)
UPS-GXT (VA)Cooling
System
1000 1500 2000
FAC-190 15 15 20
FAC-360 15 15 20
UAS/ECM-42 20 -- --
UAS/ECM-62 30 30 --
UAS/ECM-80* ECM-80 - 20 Amp / UPS-Load - 20 Amp
*LGH ECM-80 systems provided with separate
ECM & UPS power connections.
60 Hz Systems with NO UPS - Service Connection Selection
If a UPS is not supplied, the system power rating and plug connection are customer selected based on
the Cooling System and customer Amp load.
MAX. AVAILABLE CUSTOMER EQUIPMENT AMPS
(based on customer selected Service Connection)
SERVICE CONNECTIONCooling System
15 Amp 20 Amp 30 Amp
FAC-190 11.5 15.5 23.5
FAC-360 11 15 23
ECM-42 only -- 8 16
UAS-42 -- 7 15
ECM-62 only -- -- 12
UAS-62 -- -- 10
UAS/ECM-80* -- -- --
*Power strip is rated for 15 Amp service
50 Hz Systems with NO UPS or WITH UPS - Full Load Amp Draw
The 50 Hz LGH is provided with a cord for input power connection; an appropriate plug is to be field
supplied. Selection charts below are to be used to determine plug requirements per local codes.
FULL LOAD AMP DRAW (230V - 50Hz)
UPS-G (VA)Cooling System UPS
1000 1500 2000
FAC-190 .5 4.5 6.5 8.7
FAC-360 1 5 7 9.2
UAS/ECM-42E only 7 11 -- --
UAS/ECM-42E 7.5 11 -- --
UAS/ECM-62E only 9 13 15 --
UAS/ECM-62E 9 13 15 --
UAS/ECM-80E 9 13 15 17
Note: Power strip is rated for 10 Amp service