Liebert LDM Network Card User Manual


 
Operation
26
5.5.10 Edit the Breaker Properties
The Breaker Properties box displays the breaker name, rating, other parameters and alarm setpoints.
To view or change parameters and alarm setpoints of a breaker:
Click on the breaker in the left pane. When selected, the breaker has a yellow outline.
Refer to the following table to make changes.
When finished, click Install to Unit to upload the changes to the Liebert LDM.
Parameter Description To make a change:
Breaker
Name
The name of the selected breaker. The default
names are BREAKER #01, BREAKER #02, etc.
Click in the Breaker Name box, click Edit and
enter a name, then click Apply.
Position
The location of the selected breaker on the
panelboard.
(Cannot be edited)
Number
of Poles
The number of poles selected when the breaker was
added to the panelboard.
(Cannot be edited)
Breaker
Rating
The amperage for which the circuit breaker is rated.
The default is 20A.
Click in the Breaker Rating box, click Edit and
enter a value, then click Apply.
Phase
Overcurrent
Alarm
Percentage of the breaker rating that triggers an
overcurrent alarm. This value must be higher than
the Phase Overcurrent Warning.
Click in the Phase Overcurrent Alarm box,
click Edit and enter a value, then click Apply.
Phase
Overcurrent
Warning
Percentage of the breaker rating that triggers an
overcurrent warning. This value must be lower than
the Phase Overcurrent Warning.
Click in the Phase Overcurrent Warning box,
click Edit and enter a value, then click Apply.
Phase
Undercurrent
Alarm
Percentage of the breaker rating that triggers an
undercurrent alarm. The default is 0 (zero). Indicates
no current is flowing through the breaker—either the
breaker has tripped or the equipment has shut down.
Click in the Phase Undercurrent box, click Edit
and enter a value, then click Apply.
Neutral Current
Alarm
Percentage of the breaker that triggers a neutral
current alarm.
Click in the Neutral Current Alarm box, click
Edit and enter a value, then click Apply.
Ground Current
Alarm
Amperage that triggers a ground current alarm.
Click in the Ground Current Alarm box, click
Edit and enter a value, then click Apply.
NOTE
The configuration changes will not be stored in the Liebert LDM until the Install to Unit
button is clicked.
Breaker
Properties
Select a
Breaker
Install to Unit
(click to save
changes to
Liebert LDM)
Edit and
Apply
buttons