Installation and Commissioning
14
Figure 10 Bottom plate with cutouts
Cable and pipe openings must be sealed air-tight on completion of work.
5.4 Condensed Water Connection
If the XDK is operated below dew point, condensed water may occur. As standard there is a water con-
nection, 5/8" diameter, in the condensed water tray for drainage.
Preparations for Connecting
When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self-
filling siphon with return protection and that the condensate drain is properly sloped.
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so
that air is not drawn into or blown out of the waste pipe.
Front
Condensed
Water Cutouts
Network
Cable
Entry
Sealed Cable Cutout
Rear
Cutout for
Water Pipes
Step 1):
Remove
the air
duct
Step 2):
Remove
the cap
Step 3.)
Connect the
nipple with a drain
hose 5/8"
Condensate
connection
Step 4.)
Move and snap the
nipple with hose
into the hole