18
Battery Run Times
ENVIRONMENTAL
Operating Temperature 0°C to +40°C (+32°F to + 104°F)
Storage Temperature -15°C to +50°C (+5°F to + 122°F)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 3000 m (10,000 ft.) at 35°C (95°F) w/o derating
Audible Noise < 40 dBA, at 1 meter
AGENCY
Safety EN50091-1-1, TUV/GS listed, CE Compliance Mark
Surge EN61000-4-5, Level 3, Criteria A
ESD EN61000-4-2, Level 3, Criteria A
Susceptibility EN61000-4-3, Level 2, Criteria A
Electrical Fast Transient/
Burst
EN61000-4-4, Level 3, Criteria A
Emissions EN50091-2, Class B
Harmonics EN61000-3-2
Conducted Immunity EN61000-4-6
Flicker EN61000-3-3
Transportation ISTA Procedure 1A
Load % 500VA 650VA
595117
10 53 73
20 25 35
30 19 20
40 12 12
50 8 8
60 7 7
70 5 4
80 3 3
90 3 2
100 2 1
Note: Approximate discharge times are in minutes and
at 25°C (77°F) with resistive load.