Product Description
5
1.4 Mechanical Considerations
1.4.1 Positioning the Liebert XDP
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at
least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the
Liebert XD
™
System, SL-16655. The document is available in electronic format at Liebert’s Web site,
www.liebert.com, as well as from your local Emerson Network Power representative.
Figure 8 Dimensions
Table 1 Liebert XDP dimensions
Model
50/60Hz
Dimensional Data inches (mm) Shipping Weight, lb (kg)
A B* C D E Domestic Export
XDP160 38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 990 (449) 1067 (484)
* The dimension does not include the bezel of the disconnect switch.
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN000767
Pg. 2, Rev. 6
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5" (127mm)
1" (25mm)
5-1/2"
(140mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.