MGE UPS Systems 18/280 kVA Power Supply User Manual


 
MGE UPS SYSTEMS CleanWave - Installation and user manual Page 5/13
Version 2.1.4 – 15/01/2007 -
2.2. R
ANGE
The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).
Minimum sections
1
TYPE Power.
I
phase
max
I
neutral
Max
Total
losses
max Phases Neutral (N) Earth (PE) ( PEN
2
)
[kVA] [A] [A] [W] [mm²] [mm²] [mm²] [mm²]
CleanWave-18 18 24 43 219 4 10 4 10
CleanWave-30 30 40 72 359 10 25 10 25
CleanWave-40 40 56 101 452 16 35 16 35
CleanWave-55 55 80 144 538 25 2x 25 16 2x 25
CleanWave-90 90 128 231 616 50 2x 50 25 2x 50
CleanWave-140 140 201 361 972 95 2x 95 50 2x 95
CleanWave-180 180 264 476 1212 150 2x 150 95 2x 150
CleanWave-220 220 321 577 1565 2x 95 2x 185 95 2x 185
CleanWave-280 280 401 722 1568 2x 95 2x 240 95 2x 240
Table 4
1
According to European standards
2
If common conductor for neutral and earth (PEN conductor)