MGE UPS Systems 800 Tower Power Supply User Manual


 
Configurable function
UPS sensitivity level
Default setting
Normal
Options
High or low
3400723200/AC - Page 21
3. Operation
Configurable function
Output voltage on battery power
Upper threshold for transfer to battery power
Fader-mode cut-in threshold
Booster-mode cut-in threshold
Lower threshold for transfer to battery power
Maximum input-voltage range
Default setting
120 V
151 V
132 V
102 V
89 V
Disabled
Options
100 - 127 V
141 to 153 V
127 to 138 V
92 to 108 V
80 to 94 V
Enabled (1)
Voltage-thresholds tab
Sensitivity tab
For more information about these settings, refer to the Help function of the "UPS Driver" software.
(1) Lower threshold for transfer to battery mode = 70 V