8/69
1.8 Technical data
1.8.1 Configuration
The user can configure the card with one of the following means:
Z Web browser
Z Local serial link
Z Telnet console
Z BOOTP/DHCP
Z Mupgrade
1.8.2 Administration
Z Up to 50 workstations protected
Z Up to 15 browsers connected at the same time
Z E-mail sending configurable according to UPS alarms and transmission of a periodical report
Z Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting
down the installation
Z Control of UPS on/off switching via the HTML interface
Z Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation
and optimisation of backup time by shutting down non-priority systems
Z Adjustment of date and time via NTP server - Daylight Saving Time management
Z Protection by encrypted password.
Z Protection by secured connection SSL and SSH
Z Saving of logs in the non-volatile memory
Z Automatic language detection according to browser configuration.
Z Languages available: English / French / Spanish / German / Italian
Z On-line help available for each page
Z Card firmware updated via the network
Z Card configuration deployment on your installed base through network utility (Mupgrade)
1.8.3 Network
Z Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
Z SNMP trap port modifiable (by default = 162)
1.8.4 MIB (Management Information Base)
Z MIB IETF UPS (RFC1628) / MIB MGE V1.7
1.8.5 Environment sensor
Z Temperature measurement from 0 to 70 °C with +/- 1°C accuracy
Z Measurement of humidity from 0 to 100 % with +/- 6 % accuracy
Z Min / max time-stamped function for temperature and humidity
Z Choice of temperature readings in Celsius or Fahrenheit
Z High and low thresholds, hysteresis and offset adjustable via Web interface
Z Possibility of notification of status changes by e-mail, SMS or SNMP traps
Z Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)