MGE UPS Systems Pulsar EX 1000 Power Supply User Manual


 
Page 20 - 51031604EN/AA
3. Operation
Personalisable function
Rated UPS voltage
Rated UPS frequency
UPS tolerance for AC-power
source frequency
Overload alarm threshold
UPS restart following short-circuit
Default setting
230 V
F = 50 Hz
F ± 5%
110%
Disabled
Options
200 V - 208 V - 220 V - 240 V
60 Hz
F ± 1% to ± 10%, in 1% steps
0 to 110%, in 10% steps
Enabled (click to add check)
Personalisable function
Transfer to bypass if overload
Transfer to bypass following a fault, whatever the
conditions on the AC-power source
Default setting
Enabled
Disabled
Options
Disabled (click to remove check)
Enabled (click to add check)
"Output" tab
"Bypass" tab
by-pass
3.5 Shutdown
23
Press button 23 (return to the OFF position).
The connected equipment is no longer supplied with power.