MGE UPS Systems Pulsar TM EX30 Power Supply User Manual


 
12 Pulsar EX: E-51032278XT/AB MGE UPS SYSTEMS
P
UT
I max 15A
Vac OUT
Vac OUT
I max. 30A
FUSE
15A 120V-T
FUSE
15A 120V-T
FUSE
15A 120V-T
7b
7a
?
p
r
e
s
s
r
e
s
e
t
?
p
r
e
s
s
r
e
s
e
t
?
p
r
e
s
s
r
e
s
e
t
8
to computer
loads
U
IT
ER
5
V-T
INPUT
5
I max 15A
15A
120V T
FUSE
15A 120V-T
FUSE
15A 120V-T
?
p
r
e
s
s
r
e
s
e
t
?
p
r
e
s
s
r
e
s
e
t
utility power
receptacle
getting started
location
c observe the safety rules indicated at the
beginning of this document.
preliminary checks
c check that the "on/off" button " " on the
front is not pushed in;
c check that rating shown on the rating label
corresponds to the input voltage
specification and power requirement of the
load.
connections
c connect the AC input cord to the utility
power outlet.
c connection of the Pulsar EXB20/30
battery extension module (optional):
v check that the button "on/off" " " on the
front of the Pulsar EX20/EX30 is not pushed
in,
v disconnect the input connection cord,
v flip the circuit-breaker of the battery unit to
the right (position "O"),
v connect the battery connection cord to the
DC connector of the battery module and
connect to the Pulsar EX20/EX30,
v if the installation has 2 battery modules,
connect the second cord to the DC
connector of the second module and to the
first module,
v the use of connectors is strictly limited to
connecting the battery modules to the
Pulsar EX20/EX30. Any other connection to
these connectors is prohibited and risks
damaging the battery, not covered by
warranty,
v to start, flip the battery circuit-breaker to
the left (position "I"),
v if your installation is operated with MGE
UPS SYSTEMS software, update your
battery configuration with EX Tuner.
c connect the computer loads to output
sockets 7a or 7b .
Note 1: following connection, the battery
automatically charges, whenever plugged in.
Note 2: the batteries will provide full back-up
time after approximatively 8 hours of
recharge time.
Note 3: if site wiring fault LED 8 is lit and
buzzer sounds, line/neutral connections are
reversed.