Minuteman UPS E1000RM1U Power Supply User Manual


 
8
English
INSTALLATION PLACEMENT
The Enterprise 1U Rackmount Series is intended to be install in a temperature
controlled environment that is free of conductive contaminants. Select a loca-
tion which will provide good air circulation for the UPS at all times. Avoid loca-
tions near heating devices, water or excessive humidity, or where the UPS is
exposed to direct sunlight. Route power cords so they cannot be walked on or
damaged.
Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F)
Operating Elevation: 0 to 3,000m (0 to 10,000 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +45 degrees C (+5 to +113 degrees F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
REAR PANEL
1. The input power cord has a NEMA 5-15P Plug.
2. The input circuit breaker will trip in the event the load exceeds the UPS’s
power rating.
3. The Battery Backup output power receptacles are NEMA 5-15R type. The
output receptacles are electrically wired into two segments to support the
"Load Shedding Function". The three receptacles on the left are Segment 1
and the three receptacles on the right are Segment 2.
4. The RS232 Communications Interface Port is for UPS monitoring and con-
trol.
5. The R-J11/R-J45 modular connectors are used for 10/100 Base-T Network/
single line Phone/Fax/Modem protection.
6. The USB Communications Interface Port is for UPS monitoring and control.
7. The Dipswitches are for setting the Inverter (On-Battery) output voltage.
8. The option slot will support MINUTEMAN option cards only.