For setting up the system, the 485ADP can be connected to the following PCs.
PC series
FX
0N
FX , FX2C
PC version
Ver. 1.20 or later
Ver. 3.30 or later
Remarks
Exclusive protocol format 1 and format 4 are supported.
Exclusive protocol format 1 and format 4 are supported.
FX
0N-485ADP
FX-485ADP
As for exclusive protocol formats (1, 4) , see the 485PC-IF manual.
For connection with the PC, connect the serial port provided at the left side facing the PC basic unit and the
extension cable of the 485ADP. It must be noted however that only one special adapter (FX-8AV, FX-232ADP,
etc.) such as 485ADP can be connected to the PC.
In the case of FX-485ADPIn the case of FX0N-485ADP
FX-485ADP
MITSUBISHI
24G
24+
FG
RDA
RDB
SDASDBLINK
SG
2
WIRING
1.3 Applicable PCs
1.4 Connection with PC
The connecting method with the 485PC-IF is available in two-pair wiring and one-pair wiring, which may be
used as follows. As for connection of the 485PC-IF and computer, see the 485PC-IF manual.
Two-pair wiring is required when :
The RS-422 device is incorporated in the system configuration.
A high speed response is required (message waiting time is desired to be less than 70 ms).
The on-demand function is used (however, the system configuration must be 1 : 1).
Adding to a system already using two-pair wiring.
*See the 485PC-IF manual.
One-pair wiring is required when :
Adding to a system already using one-pair wiring.