23
4
:4
3
6
5
:3
2
:2
1
:1
:4
:3
:2
:1
Controller board
Drive circuit
Connector(CN60)
DC12V
Brown
Red
Blue
Orange
Yellow
White
M
4
6
2
3
5
1
Blue
Brown
Yellow
Orange
Red
White
Linear expansion valve
<Thermistor characteristic graph>
Room temperature thermistor (TH21)
Liquid pipe temperature thermistor (TH22)
Gas pipe temperature thermistor (TH23)
Thermistor R0=15k' ± 3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
30_F 15.8k'
50_F 9.6k'
70_F 6.0k'
80_F 4.8k'
90_F 3.9k'
100_F 3.2k'
Thermistor for
lower temperature
Linear expansion valve
10-1-2.
1 Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signals.
<Connection between the indoor controller board and the linear expansion valve>
1
273+(t-32)/1.8
1
273
0
10
20
30
40
50
0-20 20 40 60 80 100 120
< Thermistor for lower temperature >
Temperature (°F)
Resistance (k)
10-1-1. Thermistor
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.