Mitsubishi Electronics PLFY-P12 Clock User Manual


 
28
J41, J42
Wireless
remote
controller
Pair No.
SWE
Test run
for
Drain
pump
Connector Jumper
Drain pump and fan are activated simultaneously after the connector
SWE is set to ON and turn ON the power.
The connector SWE is set to OFF after test run.
<Initial setting>
Pattern A
<Initial setting>
SWE SWE
OFF ON
SWE
OFF ON
OFF ON
Under
operation
or
suspension
Under
operation
Setting pattern
J41 J42
Indoor controller
Jumper wire
Pair No. of wireless
remote controller +
Initial setting
A
B
D
C
Cut
Cut
Cut
Cut
0
1
3
2
+Pair No.4-9 of wireless remote controller is setting pattern D.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
Model No.
Temperature
button
SET button
Pair No.
Minute
button
• To operate each indoor unit by each remote controller when installed 2 indoor
units or more are near, Pair No. setting is necessary.
Pair No. setting is available with the 4 patterns (Setting patters A to D).
Make setting for J41, J42 of indoor controller board and the Pair No. of
wireless remote controller.
• You may not set it when operating it by one remote controller.
Setting for indoor unit
Jumper wire J41, J42 on the indoor controller board are cut according to
the table below.
Wireless remote controller Pair No.:
Setting operation
1. Press the SET button (using a pointed implement). Check that the
remote controller's display has stopped before continuing.
MODEL SELECT
blinks, and the model No. (3 digits) appears (steadily-lit).
2. Press the MINUTE button twice. The pair number appears flashing.
3. Press the temperature buttons to select the pair number to set.
4. Press the SET button (using a pointed implement). The set Pair No. is
displayed (steadily-lit) for 3 seconds, then disappears.
Indoor controller board
Indoor controller board
Switch Pole Operation by switch Remarks
Effective
timing