Mitsubishi Electronics PLFY-P15 Clock User Manual


 
15
MICROPROCESSOR CONTROL9
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ûFûC
ûFûC
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
INDOOR UNIT CONTROL
9-1. COOL OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display COOL.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Cooling 67 to 87°F
Control modes
Control details
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
• Room temperature desired temperature + 2°F
···Thermo ON
• Room temperature desired temperature
···Thermo OFF
1-2. Anti-freezing control
Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16
minutes from compressors start up, anti-freezing control
starts and the thermo OFF.
Released condition : The timer which prevents reactivating is set for 3 minutes,
and anti-freezing control is cancelled when any one of the
following conditions is satisfied.
 Liquid pipe temp. (TH22) turns 50°F or above.
 The condition of the thermo OFF has become complete
by thermoregulating, etc.
 The operation modes became mode other than COOL.
The operation stopped.
By the remote controller setting (switch of 4 speeds+Auto)
When [Auto] is set, fan speed is changed depending on the value of:
Room temperature - Desired temperature
2. Fan
1. Thermoregulating
function
Remarks
Type
Fan speed notch
[Low], [Med2], [Med1], [High], [Auto]
4 speeds + Auto type
To be continued on the next page.