National Instruments SCC-AI13 Network Card User Manual


 
SCC-AI Series Isolated Analog Input Modules User Guide 4 ni.com
You can download NI documents from ni.com/manuals. To download
the latest version of NI-DAQmx, click Download Software at
ni.com.
Device Specific Information
Note For general SCC module installation and signal connection information, and
information about the SC-2345/2350 or SCC-68, refer to the SCC Quick Start Guide,
available for download at
ni.com/manuals.
Installing the Module
Caution Refer to the Read Me First: Safety and Radio-Frequency Interference document
before removing equipment covers or connecting/disconnecting any signal wires.
You can plug the SCC-AI into any analog input socket on the
SC-2345/2350 or SCC-68. The socket you choose determines which
E/M Series DAQ device channels receive the SCC-AI signals.
For single-stage input conditioning, plug the SCC-AI into any slot of the
SC-68, or any socket of the SC-2345/2350 J(X+1), where X is 0 to 7.
Connect the input signals to the module as described in the Connecting the
Input Signals section.
If you use the SCC-AI in a dual-stage configuration in an SC-2345, the
SCC-AI must be the first-stage module. Plug it into any socket J(X+9) and
plug the second-stage SCC into socket J(X+1), where X is 0 to 7. Connect
the input signals to the SCC-AI as described in the Connecting the Input
Signals section. The SC-2345 connects the output signals of the first-stage
SCC to the inputs of the second-stage SCC. An example of dual-stage
conditioning is an SCC-AI02 followed by an SCC-FV01 frequency input
module.
Sockets J9 to J16 of the SC-2345 are also available for digital input/output
(DIO) conditioning or control. Refer to the SC-2345/2350 User Manual
for more information about configuring, connecting, and installing SCC
modules.