Rev. 041008
5
HAZARDOUS LOCATION INSTALLATION REQUIREMENTS
1. This equipment is suitable for use in Class I, Div 2, Groups A, B, C, and D, or unclassified or non-
hazardous locations only.
2. WARNING: Explosion Hazard - Substitution of components may impair suitability for Class I,
Division 2.
3. WARNING: Explosion hazard, do not disconnect while the circuit is live or unless the area is known to be
non-hazardous.
4. WARNING: Explosion Hazard - Do not remove or replace the device unless power has been switched off
or the area is known to be non-hazardous.
5. Use 60/75ºC rated Copper wire, (0.22Nm) 2 inch-lbs Tightening torque for field installed connectors.
6. WARNING: Install only in accordance with Local & National Codes of Authorities Having Jurisdiction.
7. Class I, Div 2 installations require that all devices connected to this product must be UL listed for the area in
which it is installed.
8. WARNING: Damage may occur to the RJ-45 port of the powered device (PD), if the switch is not
powered down before disconnecting the Cat5 cable.