Omron G3M Switch User Manual


 
3
Solid State Relay G3M
J CHARACTERISTICS
Item G3M-102PL-US (-4) G3M-202P(L)-US (-4) G3M-203P(L) (-4)
G3M-205P(L) (-4)
Operate time 1 ms max. (1/2 of load power source cycle + 1 ms max. for G3M-202P, G3M-203P, G3M-205P)
Release time 1/2 of load power source cycle + 1 ms max.
Output ON voltage drop 1.6 V (RMS) max.
Leakage current 2 mA max. (at 100 V AC) 2 mA max. (at 100 V AC)
5 mA max. (at 200 V AC)
1.5 mA (at 200 VAC)
Insulation resistance 1,000 Mmin. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min 2,500 VAC, 50/60 Hz for 1 min
Vibration resistance Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance Malfunction: 1,000 m/s
2
{approx. 100G}
Ambient temperature Operating: --30°Cto80°C (with no icing or condensation)
Storage: --30°C to 100°C (with no icing or condensation)
Approved standards UL508 File No.E64562/CSA C22.2 (No.0, No.14) File No. LR35535
TÜV R9551055 (EN60950)
Ambient humidity Operating: 45% to 85%
Weight Approx. 15 g
Approx. 25 g
J APPROVALS
UL (File No. E64562)/CSA (File No. LR35535)
Input V oltage SSR Type Load Rating
5, 12, 24 VDC
With Suffixes 102 and
US or UTU
2 A, 125 V AC, Resistive 250 W, 125 VAC, Tungsten 2 A FLA, 12 A LRA, 125 VAC
With Suffixes 202 and
US
2 A, 250 V AC, Resistive 500 W, 250 VAC, Tungsten 2 A FLA, 12 A LRA, 250 VAC
With Suffixes 202
UTU, UTU-1, and
UTU-2
2 A, 250 V AC, Resistive 250 W, 250 VAC, Tungsten 1 FLA, 6 LRA, 250 VAC
With Suffixes 103 and
US or UTU
3 A, 125 V AC, Resistive 375 W, 125 VAC, Tungsten 1.5 A FLA, 9 A LRA, 125 VAC
With Suffixes 203 and
US or UTU
3 A, 250 V AC, Resistive 750 W, 250 VAC, Tungsten 1.5 A FLA, 9 A LRA, 250 VAC
With Suffix 105 5 A, 125 VAC, Resistive 625 W, 125 VAC, Tungsten 2.5 A FLA, 15 A LRA, 125 VAC
With Suffix 205 5 A, 250 VAC, Resistive 1250 W, 250 VAC, Tungsten 2.5 A FLA, 15 A LRA, 250 VAC