MODEL AMPACITY DC BREAKER DC FUSE
FX2012MT 200 amps OBDC-250 Class T-400 (Mobile Only)
FX2024MT 175 amps OBDC-175 Class T-300 (Mobile Only)
FX2532MT 175 amps OBDC-175 Class T-300 (Mobile Only)
FX2548T 100 amps OBDC-100 Not Recommended
VFX2812M 200 amps OBDC-250 Class T-400 (Mobile Only)
VFX3524M 260 amps OBDC-250 Class T-400 (Mobile Only)
VFX3232M 175 amps OBDC-175 Class T-300 (Mobile Only)
VFX3648 175 amps OBDC-175 Not Recommended
GTFX 2524 125 amps OBDC-175 DO NOT USE
GTFX 3048 75 amps OBDC-100 DO NOT USE
GVFX 3524 175 amps OBDC-250 DO NOT USE
GVFX 3648 90 amps OBDC-125 DO NOT USE
MAXIMUM OVERCURRENT PROTECTION AMPACITY
This rating speci es the proper overcurrent protection ampacity.
• OBB breakers are panel-mount circuit breakers.
• Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.
• FXs used in home installations should use properly sized DC circuit breakers.
• A DC breaker includes both overcurrent protection and disconnect capability.
• OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.