Panduit DPOE24S1X Network Card User Manual


 
PANDUIT® DPoE™ Power Patch Panel User’s Guide Issue 2.2
Part Number: PN378A
18
LED Color Port LED Status Description Status of Power Ports
Red Solid The system has failed to determine
the PD power requirements for this
port. Perhaps this PD is not an
802.3af-2003 compliant or Cisco
legacy power device. It could also
be a port configured for 802.3af-
2003 and an alternate PoE device
has been connected.
Also, pins (4,5) & (7,8) of a
connected non-powered device
such as a PC may be terminated in
such a way that the power patch
panel attempts to detect it as a PD.
The Element Manager may be used
to turn detection off (see Element
Manager section) to this port so no
further checks occur. The LED will
extinguish.
This may also be an indication of a
short in the wiring. The connections
at both ends of the horizontal
cabling should be checked to
ensure proper wiring has been
followed.
Power is NOT being
delivered down this port on
the panel.
Table 10: Network Status LED Indications
LED Color Network LED
Status
Description Notes
Off Off No connection to the
management system.
If the system is otherwise operating
normally and an Ethernet 10/100 cable
is connected, this could be an issue
with the panel's management interface.
Green Flashing The management link on the
DPoE™ Power Patch Panel
is configured correctly and
communication messages are
currently being processed.
Normal operation.
Green Solid The management link on the
DPoE™ Power Patch Panel
is configured correctly, but no
communication messages are
currently being processed
(i.e., the link is idle).
Normal operation.
Amber Solid The panel is currently trying
to acquire DHCP address
information from the network.
If this persists for more than a minute or
two, the daisy chain of connections
between multiple panels may be
incorrect or there are problems at the
DHCP server.