DPOE™ Power System User Manual Part Number: PN380C
3
Table 2: DPOE™ Power Components Available from PANDUIT
PANDUIT Part Number Description
DPOEPWRB120Y Individual power supply - 120 watt power supply –
48 volt output
DPOEPWRCU Unmanaged power chassis (supports 3 rectifiers)
DPOEPWRR500 500 watt rectifier for use in power chassis
DPOEPWRR1250 1250 watt rectifier for use in power chassis
DPOEPWRF7.5 7.5 amp fuse (package of 8)
DPOEPWRF5 5 amp fuse (package of 4)
CORD-A Power cord for Australia
CORD-E Power cord for Europe
CORD-S15 Power cord for North America
CORD-J15 Power Cord for Japan
CORD-U Power cord for the U.K.
Heat Dissipation
The following table displays the maximum and typical British Thermal Units per hour (BTU/hr) of heat
dissipated from each rectifier. The maximum is calculated at 90 VAC, and typical is calculated at 230
VAC.
Table 3: Heat Dissipation
Part Number Typical BTU/hr Max BTU/hr
DPoEPWRR500 249 410
DPoEPWRR1250 451 833
AC Input Wiring
The DPOE™ Power System chassis uses an individual AC feed architecture (See
Figure 2: Individual AC Feed Wiring
Architecture), which requires one AC feed per rectifier. Up to three,
AC connections are made using the IEC320 receptacles on the rear of the chassis (See
Figure 8: Chassis (Rear View) - AC
Connections).
Connect each feed, using the appropriate power cord as listed in Table 2: DPoE™
Power Components
Available into the appropriate receptacle on the back of the system. Cord securing brackets are included
to secure the AC plugs to the chassis (See Figure 9: Securing Cord Bracket to Chassis
).