OPERATION
EATON Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com
44
4. On the PANEL CONFIG screen, set the panel’s meter settings:
Default Range Meter Setting Description
3 3 PHASES Number of phases
42 0–42
(even numbers)
BREAKERS Number of branch circuit
breakers in the panel
100 0–1200 RATING Panel breaker rating (in amps)
(see Note 1)
STANDARD STANDARD
COLUMN
PNL LAYOUT Panel layout
(see Note 2)
NOTE 1 Setting the panel breaker rating to 0 silences all main panel breaker
alarms and zeroes the panel percent current levels.
NOTE 2 Changing panel layout erases all branch circuit breaker configurations.
To reset all values on the screen to defaults, set the RESET value to
YES.
5. Select OK.
6. Repeat Steps 3 to 5 for each panel containing branch circuit
breakers to configure.
7. When all panel configuration is complete, select the
button
repeatedly to reach the main menu.
8. If all configuration is complete, save your changes by pressing the
Reset button on the Power Xpert Gateway Card in the X−Slot
communication bay. (The card automatically resets after five
minutes.) Otherwise, continue to Configuring Branch Circuit
Breakers" on page 46.
Configuring Panels Containing Subfeed Breakers
To configure panels containing subfeed breakers (up to 12 per panel):
1. If not already obtained, access the System Setup Level 1 password
level. See Accessing Configuration" on page 43.
2. From the main menu, select METER then PANEL.
3. On the PANEL screen, select the panel number (PNL) to configure,
and then select CONFIG.