Rackmount Solutions VA 20000 Power Supply User Manual


 
Chloride Active and E-Series UPS User Manual 39
13.4 Commissioning of an External Battery Cabinet
The following table shows the designations of the battery cabinets which are available for the UPS devices.
Table 8. External Battery Packs
Model Cabinet Batteries
E61 (E41) BPE61 2x (20 x 7. 2 Ah)
E101 (E81)/
E203 (E153)
BPE101 1x (20 x 38 Ah)
Disconnect the UPS from the mains and the loads from the UPS.
CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.
CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.
Connect the battery cabinet types BP1000, BP3000 and BPE61 to the UPS using the supplied cable. The
connection scheme is shown in the figures below. With type BPE101, make the hard-wired connection
between UPS and the battery cabinet (see figures 28 and 29 on page 40).
Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.
NOTE: Battery charging times may be longer when using an external battery cabinet.
Battery Plug for Connection of
an
Additional Battery Extension
Fig. 27: Connection of an External Battery Cabinet to Type E61