6 Type Tests
6.1 IEC 61850-3 Type Tests
Test Description Test Levels
Severity
Levels
Enclosure Contact +/- 8kV 4
IEC 61000-4-2 ESD
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
Signal ports +/- 4kV @ 2.5kHz x
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
IEC 61000-4-4
Burst (Fast
Transient)
Earth ground ports +/- 4kV 4
Signal ports
+/- 4kV line-to-earth, +/- 2kV line-to-
line
4
D.C. Power ports
+/- 2kV line-to-earth, +/- 1kV line-to-
line
3
IEC 61000-4-5 Surge
A.C. Power ports
+/- 4kV line-to-earth, +/- 2kV line-to-
line
4
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports 10V 3
IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s N/A
D.C. Power ports
30% for 0.1s, 60% for 0.1s, 100% for
0.05s
N/A
IEC 61000-4-29
30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11
Voltage Dips &
Interrupts
A.C. Power ports
100% for 5 periods, 100% for 50
periods
2
N/A
Signal ports
2.5kV common, 1kV differential mode
@ 1MHz
3
D.C. Power ports
2.5kV common, 1kV differential mode
@ 1MHz
3
IEC 61000-4-12
Damped
Oscillatory
A.C. Power ports
2.5kV common, 1kV differential mode
@ 1MHz
3
Signal ports 30V Continuous, 300V for 1s 4
IEC 61000-4-16
Mains Frequency
Voltage
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17
Ripple on D.C.
Power Supply
D.C. Power ports 10% 3
Signal ports 2kVac (Fail-Safe Relay output) N/A
D.C. Power ports 2kVac N/A
IEC 60255-5
Dielectric
Strength
A.C. Power ports 2kVac N/A
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
IEC 60255-5 H.V. Impulse
A.C. Power ports 5kV N/A
Table 15 - IEC 61850-3 Type Tests