SMC Networks EX122-SDN1 Network Router User Manual


 
5.EDS (Electronic Data Sheet) File
SMC CORPORATION
Doc.No.EX
##-OME0015
The EDS File is a file which described ID information on SI unit and important information in the
operation.
The DeviceNet controller or scanner automatically recognizes the SI unit by referring to the EDS File.
* Please refer to the undermentioned list when DeviceNet controller or the scanner dose not
automatically recognize the EDS File.
- 12 -
$ Electronic Data Sheet File for
$ SMC EX120-SDN1 Serial Interface Unit
[File]
DescText = "SMC EX120-SDN1 EDS File";
CreateDate = 05-20-1999; $ created
CreateTime = 10:30:00;
Revision = 1.1; $ Revision of EDS
[Device]
VendCode = 7;
VendName = "SMC Corp.";
ProdType = 16;
ProdTypeStr = "General Motion Controller";
ProdCode = 288;
MajRev = 2; $ Device Major Revision
MinRev = 7; $ Device Minor Revision
ProdName = "Valve Manifold SIU";
Catalog = "EX120-SDN1";
[IO_Info]
Default = 0x0001; $ Poll(Bit 0)
PollInfo = 0x0001 , 1 , 1; $ Prod. Cnxn=1
$ Cons. Cnxn=1
Input1 = 2, $ 2 byte
0, $ All bits are significant
0x0001, $ Poll Only Connection
"Solenoid Status", $ Name String
6, $ Path Size
"20 04 24 05 30 03", $ Assy Obj Inst 5 Attr 3
""; $ Help String
Output1 = 2, $ 2 byte
0, $ All bits are significant
0x0001, $ Poll Only Connection
"Solenoid Output", $ Name String
6, $ Path Size
"20 04 24 23 30 03", $ Assy Obj Inst 23 Attr 3
""; $ Help String