TDK FPS1000-12 Power Supply User Manual


 
47
Fig 19-1: Remote sensing, three load.
CHAPTER 19 BASIC CONNECTIONS FOR OPERATION FPS-T1U RACK
19.1 Connecting Single Load, Remote Sensing
Remote sensing is used in cases where the load regulation is important at the load terminals. Use twisted
or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected
to the ground at one point, either the power supply side or the load. The optimal point for the shield ground
should be determined by experimentation. Refer to the power supply specifications for the maximum
voltage drop allowed at the load wires.
FPS-T1U
FPS-1000 Module A
Sense lines
Twisted pairs
Load line. Up to 1V drop.
Load line.
Up to 1V drop.
LOAD
+V
+S
-S
-V
J1-8
J1-7
+V
-V
LOAD
+V
+S
-S
-V
J2-8
J2-7
+V
-V
LOAD
+V
+S
-S
-V
J3-8
J3-7
+V
-V
FPS-1000 Module B
FPS-1000 Module C
J1(A)-12
J3(C)-3
ON/
OFF_1
A
J2(B)-12
J2(B)-3
ON/
OFF_1
B
J3(C)-12
J1(A)-3
ON/
OFF_1
C
In Local sense applications, the +/- sense have to be connected to the
+/-Local Sense terminals of the FPS-T1U prior to operating the FPS1000 units plugged in.
*
Fig 19-3
FPS-T1U
FPS-1000 Module A
FPS-1000 Module B
FPS-1000 Module C
ON OFF
ON OFF
ON OFF
J1(A)-12
J2(B)-12
J3(C)-12
J1(A)-3
J2(B)-3
J3(C)-3
FPS-T1U
FPS-1000 Module A
FPS-1000 Module B
FPS-1000 Module C
OFF ON
OFF ON
OFF ON
J1(A)-4
J2(B)-4
J3(C)-4
J1(A)-3
J2(B)-3
J3(C)-3
ON/
OFF
SLCT
J1(A)-12
J3(C)-13
ON/
OFF1
A
ON/
OFF
SLCT
J2(B)-12
J2(B)-13
ON/
OFF1
B
ON/
OFF
SLCT
J3(C)-12
J1(A)-13
ON/
OFF1
C
Fig 19-2
Connection for negative logic:
Closed: On Open: Off
Factory default: ON/OFF Control_1
Connection for positive logic:
Closed: Off Open: On
ON/OFF Control_1 ON/OFF Control_2
19.2 On/Off control
Fig 19-2 and Fig 19.3 shows typical connection for individual On/Off control of each installed FPS1000 unit.
FPS-T1U Instruction Manual