19
FPS1000 Instruction Manual
7.2 I
2
C Interface Specifications
7.2.1 General specifications
1. Clock frequency: 100KHz
2. Address lines: Three (A0, A1, A2). Support 8 power supply modules
7.2.2 Output voltage measurement
7.2.3 Output current measurement
7.2.4 Internal temperature measurement
7.2.5 EEPROM
Model name, Serial no., Revision, Manufacture. Name, Output voltage,
Date, Country of manufacturing, Check-Sum
7.2.6 Status register
1. Register type: PCF8574, Philips, or equivalent.
2. Register content: DC Fail, Over-Temperature Protection (OTP)
Temperature Alarm, Fan Fail, AC Fail
3. Measurement range: 0-100°C
1. EEPROM type: AT24C02AN-10S , Atmel, or equivalent
2. EEPROM data:
1. Measurement accuracy: +/-3°C
2. Measurement resolution: 8 bits
2. Measurement resolution: 8 bits
3. Measurement range: 0~25.0A for 48V model
/
0~50A for 32V & 24V models
3. Measurement range:
0~60.0V for 48V model / 0~40.0V for 32V model / 0-30.0V for 24V model.
1. Measurement accuracy: +/-10% of full scale
1. Measurement accuracy: +/-2% of full scale
2. Measurement resolution: 8 bits
CHAPTER 7 I
2
C BUS INTERFACE OPTION
7.1 Introduction
The I
2
C interface option includes facilities to monitor operating parameters of the power supply. The parameters
are then transferred to the host PC if demanded, over a standard I
2
C bus.
The following data can be monitored for the individual units connected to the I
2
C bus:
1. Status of the unit.
2. Actual output voltage, output current and internal temperature of the unit.
3. Manufacturing related data (model, serial number, manufacturing date etc…).
7.1.1 Addressing (A0, A1, A2).
Three address lines allow up to eight FPS1000 units to be addressed on a single I
2
C bus. The address lines are
internally pulled-up to +5V by resistors. Addressing of a unit is achieved by hard-wiring an address line to the
-Sense to set it to "0" or leaving the address line open to set it to "1".
7.1.2 Serial clock
This line is clocked by the processor which controls the I
2
C bus. It should be connected to +5V (referenced to -Sense)
via a pull-up resistor of 2KΩ. The I
2
C interface is designed to run with a serial clock speed of 100KHz.
7.1.3 Serial dataThis line is a bidirectional data line. It should be connected to +5V
(referenced to -Sense) via a pull-up resistor of 2KΩ.
CAUTION
The I
2
C bus address lines, serial clock and data are
referenced to the -Sense potential. When using series
connection of FPS1000 units, do not connect the I
2
C lines
of the units together.