TDK FPS1000-48 Power Supply User Manual


 
28
10.7.5 Control and monitoring signals connector
Current sharing signal. When FPS-S1U racks are connected in parallel, the CS pins
of the units should be connected to allow current balance between units.
CS9
Connection for output voltage trimming of FPS1000 unit "C". The voltage can be
trimmed within its range specifications.
V_TRIM_C10
Return for the following control and supervisory signals: On/Off, DC_OK,
Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated
from the output terminals.
SIGNAL_RETURN11
17 NC
18 NC
19 NC
Open collector signal, referenced to pin 11 (Signal Return). On when the output voltage
of FPS1000 unit "C” is higher than 80%+/-5%. The maximum sink current: 10mA
and the maximum external voltage is 15V.
DC_OK_C12
Positive sensing. The +Sense signal should be connected to the positive terminal of
the load. The +Sense and -Sense leads should be twisted pair to minimize noise pick-
up effect. The maximum load wires drop compensation is 1V/wire.
+SENSE13
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "B" is 85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_B14
Turns the output of FPS1000 unit "B" to On and Off by electrical signal or dry contact
between pin 15 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open:
Off. The maximum source current is 2.6mA.
ON/OFF_B15
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "A" is 85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_A16
Not connected
Not connected
Not connected
Serial Clock used in the I
2
C interface option. Refer to the I
2
C interface description in
the Chapter 7 in this Instruction Manual.
SCL (I
2
C)20
Serial Data used in the I
2
C interface option. Refer to the I
2
C interface description in
the Chapter 7 in this Instruction Manual.
SDA (I
2
C)21
Negative sensing. The -Sense signal should be connected to the negative terminal
of the load. The -Sense and +Sense leads should be twisted pair to minimize noise
pick-up effect. The maximum load wires drop compensation is 1V/wire.
-SENSE22
Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature
of FPS1000 unit "C" is within safe limit, Off approx 10°C below Thermal shut down. The
maximum sink current is 10mA and the maximum external voltage is 15V.
TEMP_ALARM_C23
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage
of FPS1000 unit "C" is 85Vrms. The maximum sink current is 10mA, and the maximum
external voltage is 15Vdc.
AC_FAIL_C24
Turns the output of FPS1000 unit "C" to On and Off by electrical signal or dry contact
between pin 25 and pin 11 (Signal Return). 0~0.6V or Short: On, 2~15V or Open: Off.
The maximum source current is 2.6mA.
ON/OFF_C25