D. Battery Test Function
The UPS shall be provided with a “Battery Test” pushbutton to periodically
check the condition of the batteries. Upon detection of a battery problem,
the UPS shall notify the user of this condition allowing the user to perform
a detailed check of the battery string.
7.0 SERVICE AND WARRANTY
A. Reliability
System mission reliability 240,000** hours and including bypass MTBF
(Mean-Time-Between-Failure) shall be in excess of 3,000,000**hours.
B. Maintainability
Calculated and demonstrated MTTR (Mean-Time-To-Repair) shall be 30
minutes including time to diagnose the problem and replace subassembly.
C. Warranty
The UPS system shall be provided with a comprehensive three-year on-
site warranty (when purchased with a Factory-Authorized Start-up).
The warranty shall cover parts, labor, travel and freight for the UPS. The
battery system has a full 2 year warranty with 8 years prorata total of 10
years warranty. Typical on-site response time shall be 4 hours (24 hours
maximum). The warranty period shall expire three years for UPS and two
years for the battery system from date of shipment from manufacturer’s
facility.
*Specification subject to change without notices.
**Times are accurate provided normal Preventative Maintenance procedures are