4200FA XT1
September 6, 2004
9
B. Matching Battery Enclosure
The battery cabinet shall consist of a freestanding, matching NEMA1
enclosure equipped with casters and leveling feet. The maximum overall
dimensions and weights shall be as follows:
UPS Size Dimensions Weight Runtimes
50 kVA 30”L x 32”W x 59.8”H ~1,832 lbs. 4-29 Min
C. Cable Entry
The UPS shall be provided with cable entry from the bottom, top and rear
of the UPS enclosure.
D. Ventilation and Maintenance Requirements
The UPS shall require the following minimum space for ventilation and
maintenance: 28” (front), 18” (top), 6” (rear), and 0” (side).
6.0 STANDARD FEATURES
A. Emergency Power Off (EPO)
Emergency Power Off (EPO) terminals which trip open the UPS and
battery circuit breakers.
B. RS232 Communication Interface
Serial data link will enable the UPS to interface with a computer to
provide power status and diagnostic information.
C. DB9 Dry Contact interface
The following normally open dry contacts shall be provided through a DB9
male connector located inside the front door:
1) UPS On
2) Bypass Active
3) Input Power Loss
4) Battery Voltage Low