TOSHIBA
G
7
APPLICATION GUIDELINE 8.0
* For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
Configuring Analog Inputs
Introduction
The G7 allows several parameters to be controlled by either a 4-20[mA] or 0-10[V] analog input.
These parameters include upper limit frequency, acceleration/ deceleration time, and torque boost.
This application note will walk you through all of the steps necessary to configure the G7’s analog
inputs. The functioning of the controlled parameters will also be discussed.
Before starting, you should consider that several parameters might be controlled by a single input.
Care should be taken to ensure that only the desired parameters are being controlled by the analog
inputs, and that these parameters are being controlled in the appropriate manner
Connections
Programming
Parameter Location Default Value New Value
Upper Limit Frequency
Adjustment
Program → Terminal Selection
Parameters → Analog Input Functions
Disabled Use RR*
Acceleration Time Adjustment
Program → Terminal Selection
Parameters → Analog Input Functions
Disabled Use RR*
Deceleration Time Adjustment
Program → Terminal Selection
Parameters → Analog Input Functions
Disabled Use RR*