Trane CCUN 205-211 Network Card User Manual


 
Diagnostics
CG-SVU02B-E430
Comm Loss:
Suction Pressure Transducer
Circuit Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Ext Chilled/Hot Wtr Setpoint
Chiller Warning
and Special
Action
Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Chilled/Hot Water
Setpoint source and revert to the next higher priority for
setpoint arbitration
Remote
Comm Loss:
External Demand Limit
Setpoint
Chiller Warning
and Special
Action
Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Demand Limit Setpoint
source and revert to the next higher priority for setpoint
arbitration
Remote
Comm Loss:
Auxiliary Setpoint Command
Chiller Warning
and Special
Action
Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the Auxiliary Setpoint and revert to the
Chilled Water Setpoint based on setpoint arbitration
Remote
Comm Loss:
High Pressure Cutout Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Evaporator Water Flow Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Condenser Water Flow Switch
Chiller Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Local BAS Interface
Chiller Warning
and Special
Action
NonLatch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Use the
last values sent from BAS
Remote
Comm Loss:
Solenoid Valve
Circuit Normal Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Motor Temp/Overload
Cprsr Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Compressor Run Command
Cprsr Immediate Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Comm Loss:
Protection Module Cprsr
Circuit Warning Latch All Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote