Trane CH530 Network Card User Manual


 
DynaView Interface
CG-SVU02B-E414
Table 2 - Circuit Level Operating Modes:
Circuit Level Mode
Top Level Mode Description
Stopped The circuit is not running, and cannot run without
intervention.
Stopped Sub Modes Description
Diagnostic Shutdown - Manual Reset The circuit has been shutdown on a latching diagnostic.
Front Panel Circuit Lockout The circuit is manually locked out by the circuit lockout setting
- the nonvolatile lockout setting is accessible through either
the DynaView or TechView.
Circuit Level Mode
Top Level Mode Description
Run Inhibit The given circuit is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or
diagnostic condition is cleared.
Run Inhibit Sub Modes Description
Diagnostic Shutdown - Auto Reset The circuit has been shutdown on a diagnostic that may clear
automatically.
Condenser Pressure Limit The circuit is being inhibited from starting due to high
condenser pressure.
Circuit Level Mode
Top Level Mode Description
Auto The circuit is not currently running but can be expected to
start at any moment given that the proper conditions are
satisfied.
Auto Sub Modes Description
No Circuit Sub-Modes
Circuit Level Mode
Top Level Mode Description
Waiting to Start The chiller is going through the necessary steps to allow the
lead circuit to start.
Waiting to Start Sub Modes Description
No Circuit Sub-Modes
Circuit Level Mode
Top Level Mode Description
Running The compressor on the given circuit is currently running.
Running Sub Modes Description
No Circuit Sub-Modes