7
Specifications
Storage & Service
Storage
Turn your UPS OFF: first engage the ON/Standby Switch and release it to place
your UPS in the “Standby” mode; then set the System Enable Switch (Jumper #4,
UPS rear panel) to "DISABLE" (down); finally, disconnect the UPS power cord
from the wall outlet. If you plan on storing your UPS for an extended period of
time, recharge the UPS batteries once every three months. Follow steps #1 and
#3 in the Quick Installation section and allow the UPS to charge from 4 to 6 hours.
If you leave your UPS batteries discharged for an extended period of time, they
will suffer permanent loss of capacity.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the
ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter
describing the symptoms of the problem. If the UPS is within the 2 year warranty
period, enclose a copy of your sales receipt.
Smart 2200XLT
Output Capacity (VA/Watts): 2200/1750
Battery Runtime (Half Load/Full Load) Minutes: 27+/11+*
Battery Recharge Time: 2-4 hrs.*
Approvals: UL, cUL
Nominal Input Voltage/Frequency: 208V/60 Hz
On-Line Input Voltage Range: 173-250 volts
Voltage-Regulated Output Voltage Range: 230V ± 9%
On-Battery Output Voltage Range: 230V ± 5%
Output Waveform —Line Mode: filtered sinewave
Output Waveform —Battery Mode: PWM sine wave
AC Surge Suppression : exceeds IEEE 587
Cat. A & B standards
AC Noise Attenuation: >40 dB
AC Protection Modes: H to N, H to G, N to G
*Runtime can be extended with the connection of the appropriate Tripp Lite external battery packs. With the addition of
external battery packs, battery recharge time will increase.
9911081 230V Smartpro 2200T OM.p65 11/24/99, 12:00 PM7