5
Configuration
CONFIGURATION DIP SWITCH SETTINGS
DIP SWITCH GROUP A (All models)
BATTERY TYPE / VOLTAGE POINT
Using a small tool, set the 4 "Battery Type / Voltage Point" Configuration DIP Switches, Group A
(located on the front panel of your APS; see Diagram 1, p. 33) to select battery type and set the
voltage range outside of which your APS will switch to battery power.
• Select Battery Type
(DIP Switch #1, Group A)
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded
or damaged over an extended period of time. See "Battery Selection," page 7 for more information.
Battery Type Switch Position
Gel Cell (Sealed) Battery............................. Up
Wet Cell (Vented) Battery ...........................Down*
• Select High AC Switch To Battery Voltage Point
(DIP Switch #2, Group A)
Voltage Switch Position
264V.............................................................Up
259V.............................................................Down*
• Select Low AC Switch To Battery Voltage Point
(DIP Switches #4, Group A & #3, Group A)
Most loads will perform adequately when your APS’s High AC Voltage Point DIP Switch #2 is set
to 259V and its Low AC Voltage Point DIP Switches #3 and #4 are set to 182V. However, if your
APS frequently switches to battery power due to momentary high/low line voltage swings that would
have little effect on equipment operation, you may wish to adjust these settings. By raising the High
AC Voltage Switch to Battery point and/or lowering the Low AC Voltage Switch to Battery Point, you
may reduce the number of times your APS switches to battery due to voltage swings.
* Factory default settings.
144V*
#4 Down
& #3 Down
163V
#4 Down & #3 Up
182V
#4 Up & #3 Down
201V
#4 Up & #3 Up
Gell
Cell
Wet
Cell*
264V
259V*
9906058 230V APS MV-cabinet--English.p65 3/21/00, 4:29 PM5