Tripp Lite APSX6048VR Power Supply User Manual


 
10
AC Input/Output Connection
AC Generator Input
To avoid overloading your Inverter/Charger, be sure to match the power requirements of the equipment you plan to run at any one time (add their
total watts) with the output wattage capacity of your Inverter/Charger model. When figuring the power requirements of your equipment, do

pumps, start and stop
intermittently according to demand, requiring “peak” wattage at multiple, unpredictable times during operation.
Ground*
 
ground terminals
1
.
 
2
to earth ground.
ACInput
 Connect the incoming hot wire to the input hot
terminal
3
.
 
terminal
4
.
ACOutput
 Connect the outgoing hot wire to the output hot
terminal
5
.
 
terminal
6
.

* If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must
be bonded to the main ground lug on the unit. In any case, the incoming conduit must be
bonded to earth ground, and the incoming conduit must be bonded to the outgoing conduit.
2
• DoubleBoost
Feature
Tripp Lite Inverter/Chargers deliver up to twice their nameplate

needed to cold start heavy-duty tools and equipment.
• OverPower
Feature
        


tools and equipment.
* For best results, utilize for as short a duration as possible, ensure that battery bank
and cabling are able to provide full nominal DC voltage under load, and allow the
inverter/charger to cool completely before and after utilization.
3
1
4
Warning! Consult a qualified electrician and follow all applicable electrical codes and
requirements for hardwire connection. Disconnect both DC input and AC utility supply
before attempting hardwiring. Over-current protection should be provided in accordance
with local and/or national electrical codes. Refer to nameplate on unit for input and
output current ratings. Use wire with a minimum temperature rating of 90º C. A readily
visible and adequate disconnect device must be provided.
5
 strip

conduits to each other with the ground bond connection supplied.
The inverter/charger is designed to provide heavy-duty power to both the AC output load and the DC battery charging load at the same time. The

Configuration section for switch settings). The recommended minimum VA rating for AC generator input is shown in the table below.
6
MinimumRecommendedACGeneratorVARating
AC Input Current Sharing APSX3024SW APSX6048VR
Most Limiting 3750VA 7500VA
Less Limiting 4900VA N/A
Least Limiting 6000VA N/A
No Limiting 7200VA N/A
Note:IftheappliedACloadissignificantlylessthanthatoftheInverter/Charger’sAC
outputrating,asmallersizegeneratormaybeusedbysettingthebatterychargerDIP
SwitchtothelowDCcurrentsetting.TheminimumrecommendedVAratingforthe
ACgeneratorwouldthenbetheVAneededfortheCharger(1100VAforAPSX3024SW
or2000VAforAPSX6048VR)plustheVArequiredfortheload.