Shelf 2
Shelf 3
Shelf 1 (Bottom)
To Fuse or Breaker
Termination
To UPS
Positive
To UPS
Negative
UL-Listed
Breaker
Battery
Positive
Battery
Negative
6.2 Battery and Breaker Diagrams
6. Diagrams
(
continued
)
Shelf #2
Shelf #2
Shelf #3
AC Input for
Battery Charger
To UPS Positive
To UPS Negative
Battery Positive
Battery Negative
UL Listed Breaker
Shelf #1 (Bottom)
Shelf #1 (Bottom)
To Fuse or Breaker Termination
To Fuse or Breaker Termination
Notes:
• All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 100 A, 600 VDC, 25 KAIC.
• Cabinets with breakers are shipped with the breaker in the off/open position.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
240 VDC Battery Diagram 192 VDC Battery Diagram 192/240 VDC Breaker Diagram