Specifications
Model: OMNIVS800 OMNIVS1000 OMNIVS1500XL
Series: AGOM1000USBKSR6 AGOM1000USBKSR6 AGOM4768
Input Voltage/Frequency: 120VAC / 60 Hz 120VAC / 60 Hz 120VAC / 60 Hz
On-Line Input Voltage Range: 83 - 132 volts 83 - 132 volts 75 - 147 volts
Output Capacity (VA/Watts): 800/475 1000/500 1500/940
Battery Runtime (Half Load/Full Load) Minutes: 19/6 18/5 14/5+
Battery Recharge Time: 2 - 4 hrs. 2 - 4 hrs. 2 - 4 hrs.
Approvals: UL, cUL, NOM, FCC-B UL, cUL, NOM, FCC-B TUV NOM, FCC-B
Tel/Fax/Data Protection: 1-line Tel/DSL 1-line Tel/DSL 1-line Tel/DSL/Ethernet
Output Voltage Line Mode (120VAC); Output Voltage On Battery (115VAC). Output Waveform Line Mode (filtered sinewave); Output Waveform
Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB at 1MHz); AC
Protection Modes (H to N, H to G, N to G).
+ Battery runtime for OMNIVS1500XL can be extended with the addition of a single optional Tripp Lite External Battery Pack which is not
expandable (model #: BP24V14, sold separately). An External Battery will increase both the battery runtime and the battery recharge time.
Storage
All connected equipment should be turned off, then disconnected from the UPS to avoid
battery drain. Unplug the UPS from the wall outlet; then press and hold the ON/OFF button
for one second. The UPS will be completely “OFF” (deactivated). Your UPS is now ready for
storage. If you plan on storing your UPS for an extended period of time, fully recharge the
UPS batteries once every three months by plugging the UPS into a live AC outlet and letting
the UPS charge for 4 to 6 hours. If you leave your UPS batteries discharged for an extended
period of time, they will suffer a permanent loss of capacity.
Service
A variety of Extended Warranty and On-Site Service Programs are available from Tripp Lite.
For more information on service, visit www.tripplite.com/support. Before returning your
product for service, follow these steps:
1. Review the installation and operation procedures in this manual to insure that the service
problem does not originate from a misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit
www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Product
Returns link. From here you can request a Returned Material Authorization (RMA) number,
which is required for service. This simple on-line form will ask for your unit’s model and
serial numbers, along with other general purchaser information. The RMA number, along
with shipping instructions will be emailed to you. Any damages (direct, indirect, special or
consequential) to the product incurred during shipment to Tripp Lite or an authorized
Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or
an authorized Tripp Lite service center must have transportation charges prepaid. Mark the
RMA number on the outside of the package. If the product is within its warranty period,
enclose a copy of your sales receipt. Return the product for service using an insured carrier
to the address given to you when you request the RMA.
Storage & Service
200912037 93-2248.indd 8 12/17/2009 11:06:02 AM