Tripp Lite SMART5000RT3U Power Supply User Manual


 
DC system
voltage
48V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge
rate
2-4 hours to 90%
VOLTAGE REGULATION
Voltage
regulation
description
Line-interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain
usable, computer grade output without consuming battery power
Overvoltage
correction
Input voltages between 240V and 260V AC are reduced by 12%
Direct pass
through
Input voltages between 200V and 239V AC are passed through to equipment unchanged
Brownout
correction
Input voltages between 180V and 199V AC are boosted by 12%
Severe brownout
correction
Input voltages between 151V and 179V AC are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs 5 front panel LEDs — Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE LED, 3
color OUTPUT LOAD LED, red BATTERY WARNING LED
Alarms 3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short
beeps) and low battery (continuous tone)
Switches 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge
suppression
1020 joules
AC suppression
response time
Instantaneous
EMI / RFI AC
noise suppression
Yes
PHYSICAL
Shipping weight
(lbs)
320
Shipping weight
(kg)
145.3
Unit weight (lbs) Power Module: 93 lbs. / Battery pack: 135 lbs.
Unit weight (kg) Power Module: 42.2kg / Battery Pack: 61.3kg
Unit Dimensions
(HWD/in)
Power Module 5.25 x 17.5 x 22.5, Battery Pack 5.25 x 17.5 x 22.75
Unit Dimensions
(HWD/cm)
Power Module 13.3 x 44.5 x 57.2, Battery Pack 13.3 x 44.5 x 57.8
Material of
construction
Steel
Form factors
supported
Rack (6U)
Cooling method Built-in dual cooling fans
Battery Access Includes 1 BP48V60RT3U external battery pack. External battery packs may be disconnected and replaced while the UPS
is running connected loads in line power mode.
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing