Tripp Lite SMX1200XLHG Power Supply User Manual


 
compatible)
Line-interactive voltage regulation corrects brownouts and overvoltages from 155 to 274 volts back to usable 230V output levels, without
using battery power
Full line isolation prevents shock potential and operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 1000VA/750W
27.5 min. half-load runtime (500VA/375W), 11 min. full load runtime (1000VA/750W)
6 protected outlets; 6-inch dongle with IEC C14 inlet
USB and DB9 communication ports
PowerAlert unattended shutdown software and complete cabling included
Complete surge protection, line isolation and EMI/RFI noise filtering
5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace
Battery replacement door and back panel grounding lug
2-year product warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 230V AC
Frequency
compatibility
50/60 Hz (auto-sensing)
OUTPUT
Output VA 1000
Output watts 750
Output nominal
voltage
230V AC
Output voltage
regulation
LINE MODE: Sine wave line voltage 230V (-18% / +8%)
Output frequency
regulation
LINE MODE: Passes line frequency of 50/60Hz +/-10%
Outlet quantity / type 6 IEC320 C13
INPUT
Maximum input amps 5A / 1150 watts
Input connection type IEC320 C14 inlet
Input cord length 6 inch dongle, 16 gauge
Recommended
Electrical Service
10A 230V
BATTERY
Full load runtime 11 min. (1000VA)
Half load runtime 27.5 min. (500VA)
Expandable battery
runtime
Supports extended runtime with optional BP36V15-2U (limit 1) and BP36V42-3U external battery pack (multi-pack
compatible)
DC system voltage 36V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to
maintain usable, computer grade output without consuming battery power over an input voltage range of 155 to 274V
AC.