Tripp Lite SMX700HG Power Supply User Manual


 
Severe brownout
correction
Input voltages between 155 and 182V AC are boosted by 21%
LEDS ALARMS & SWITCHES
Front panel LEDs Yes, includes 5 front-panel indicator LEDs to show battery charge level, AC line voltage levels, automatic voltage
regulation status, UPS load level and replace battery warning
Alarms 3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous
short beeps) and low battery (continuous tone)
Switches Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge suppression 340 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 45.4
Shipping weight (kg) 20.4
Unit weight (lbs) 42.1
Unit weight (kg) 18.9
Unit Dimensions
(HWD/in)
12.8 x 7.5 x 9
Unit Dimensions
(HWD/cm)
32.5 x 19.1 x 22.9
Material of
construction
PVC
Form factors
supported
Tower
Cooling method Cooling via rear-exit cooling fan
Battery Access Battery access door allows hot swap battery replacement without powering connected equipment off
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit
Operating
Temperature
+32 to +104 degrees Fahrenheit
COMMUNICATIONS
Network monitoring
port
Includes 2 built-in monitoring ports, 1-USB & 1-RS232
Software and cabling
included
PowerAlert UPS monitoring software is available via free download from www.tripplite.com for all common network and
standalone operating systems. Ships with 2 cables, 1-USB to USB & 1-DB9 to DB9
LINE / BATTERY TRANSFER
Transfer time from
line power to battery
mode
2-4 milliseconds
Low voltage transfer
to battery power
155V (resets to line power as voltage increases to 163V)
High voltage transfer
to battery power
274V (resets to line power as voltage decreases to 266V)
SPECIAL FEATURES
Cold Start Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance Attractive gray tower UPS