Tripp Lite SU10000RT3U Power Supply User Manual


 
Two sets of 4-post rackmount rails (one for each of the 3U components)
One set of tower stands for upright tower configuration
PowerAlert Software, complete cabling, owner's manual with warranty information
Features
10,000VA (10kVA) on-line, double-conversion UPS system (high-voltage input/high-voltage output)
Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected
equipment
Installs in only 6 rack spaces (3U power module/3U battery pack) with a maximum installed depth of 32.5 in.
Offers 4 min. runtime at full load (10,000VA/8000W) and 10 min. at half load (5000VA/4000W). Runtime is expandable with any number of
optional external battery packs
Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output (user selectable)
Actively converts raw incoming AC power to DC, then re-converts output to completely regulated, filtered AC output
Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V
Standard 3-wire 208V hardwire input connection
4 x NEMA L6-20R and 2 x NEMA L6-30R output receptacles
Detailed LCD panel with scroll buttons provides detailed diagnostic test information on startup and during self tests, plus real-time data on
input and output voltage, frequency (Hz), load percentage, battery charge level and more
Network-grade AC surge and noise suppression
Zero transfer time between AC and battery operation
Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown,
remote control and monitoring of UPS system and power data
Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes
PowerAlert monitoring software and complete cabling
Emergency Power Off (EPO) interface
Front panel LEDs provide at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass
mode and output power status
Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading
4-post rackmount and upright tower installation accessories included; 2POSTRMKITWM 2-post rackmount hardware accessories available
Field-replaceable, hot-swappable power module and external battery packs
Attractive all-black color scheme
2-year warranty; extended warranty and service contracts available
$250,000 connected equipment insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency
compatibility
50/60 Hz
OUTPUT
Output VA 10000
Output watts 8000
Output nominal
voltage
208V AC (200/208/220/230/240V)
Output voltage
regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total
harmonic distortion when used with computer loads
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type 4 x NEMA L6-20R, 2 x NEMA L6-30R
INPUT
Maximum input amps 200V-46.7A / 208V- 44.9A / 220V- 42.4A / 230V-40.6A / 240V-38.9A
Input connection type Hardwire
BATTERY