Tripp Lite SU10000RT3U Power Supply User Manual


 
Full load runtime 4 min. (10,000VA/8000W)
Half load runtime 10 min. (5000VA/4000W)
Connects to UPS via Included 3-wire DC cable
DC system voltage 240VDC
Typical battery
lifespan
4-6 years
Battery recharge rate Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected
nominal voltage at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within
2% of selected nominal
Brownout correction Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC,
regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs 6-LED display: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily
rotates for better viewing in rackmount or tower configurations.
Alarms Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter
fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete
Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 331
Shipping weight (kg) 150.3
Shipping Dimensions
(HWD/in)
39.75 x 31.5 x 23
Shipping Dimensions
(HWD/cm)
101 x 80 x 58.4
Unit weight (lbs) Power Module 55 lbs., Battery Pack: 136.5 lbs.
Unit weight (kg) Power Module 25 kg., Battery Pack: 62 kg
Unit Dimensions
(HWD/in)
Power Module 5.14 x 17.5 x 25, Battery Pack 5.16 x 17.5 x 25 (Installed depth of power module extends to 32.5 inches
with detachable PDU backplate installed)
Unit Dimensions
(HWD/cm)
Power Module 13.3 x 44.4 x 63.5, Battery Pack 13.4 x 40.6 x 63.5 (Installed depth of power module extends to 82.6 cm
with detachable PDU backplate installed)
Material of
construction
Steel
Form factors
supported
Rack (6U)
Cooling method Fan
Battery Access User replaceable, hot swappable external battery pack
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit / -15 to +50 Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius